Industrial UPS | 200kVA
Netcon Offers low-frequency systems that ensure compatibility with various loads, providing higher reliability and efficiency Commonly used in critical applications like data centers, medical facilities, and industrial environments, low-frequency UPS features include higher power capacity compared to highfrequency units, greater surge capacity for sudden power demands, improved voltage regulation for stable and clean power supply, and enhanced reliability to withstand harshconditions. These systems are preferred in applications where reliability, capacity, and load compatibility are essential.
| Name | Certificate |
|---|---|
| Note | View Certificate |
| INPUT | |
|---|---|
| Power factor | ≥0.97 |
| Operating voltage range (Vac) | 380/400/415 Vac (±25% ~ +20%), (3Ph + PE) |
| Operating frequency range (Hz) | 50/60 (±0.05%) |
| OUTPUT | |
| Crest factor | 3:1 |
| Output voltage (Vac) | 380/400/415 Vac (±1%), (3Ph + N + PE) |
| Efficiency (%) | 92.5 |
| Output frequency (Hz) | 50/60 (±0.05%) |
| Harmonic distortion (THDv) | ≤1 (Linear load) |
| PHYSICAL | |
| Net weight (kg) | 1030 (6P) /1715(12P) |
| Dimension W*D*H (mm) | 1200×800×1600 (6P) 1400×1000×1900 (12P) |
| Shipping weight (kg) | 1130 (6P) / 1845(12P) |
| ENVIRONMENT | |
| Operating Temperature (ºC) | 0 ~ 40 |
| Altitude (m) | <1500 |
| Storage temperature (ºC) | -25 ~ 55 |
| Humidity range (%) | 0 ~ 95 |
| Noise level (dB) | <72 |
| SYSTEM FEATURES | |
| Communication interface | RS232, RS485, EPO, Dry contact (optional), SNMP (optional) |
| LED display | Input, Inverter, Bypass, Battery, Output, Status |
| Overload | ≤110%/60min; ≤125%/10min; ≤150%/1min → Bypass |
| Optional | Harmonic filter, SNMP, LBS cables, battery temperature sensor, bypass current-sharing inductor |
| LCD display | I/O voltage, frequency, power, PF, battery status, UPS status, load %, history record |
| Transfer time (ms) | 0 |
| Technical | |
| Voltage protection range (%) | Upper: +20% (+10%, +15%, +20% adjustable); Lower: -40% (-10%, -20%, -30%, -40% adjustable) |
| Rated frequency (Hz) | 50/60 (±0.05%) |
| Capacity (kVA/kW) | 200/180 |
| Battery voltage (Vdc) | 384 |
| Frequency protection range (%) | ±10 % (±2.5%, ±5%, ±10%, ±20% adjustable) |
| Rated voltage (Vac) | 380/400/415 Vac, (3Ph + N + PE) |
| STANDARDS | |
| EMC | IEC/EN 62040-2 (IEC 61000-4-2, 61000-4-3, 61000-4-4, 61000-4-5, 61000-4-6, 61000-4-8, 61000-4-11, 61000-2-2) |
| Performance | IEC/EN 62040-3 |
| Safety | IEC/EN 62040-1; IEC 62477-1 |