Industrial UPS | 8 kVA
Design: Double conversion online, pure sine wave
Transfer Time: Zero transfer, uninterrupted output
Control: Modular design with dual CPU for high reliability
Battery: Intelligent ABM management with CC/CV charging
Bypass: Static and manual maintenance bypass
Input Range: 380V ±20%, wide frequency, generator compatible
Protection: Overload, short circuit, over-temp, battery faults
Redundancy: Parallel scalability with N+X design
Netcon Offers low-frequency systems that ensure compatibility with various loads, providing higher reliability and efficiency Commonly used in critical applications like data centers, medical facilities, and industrial environments, low-frequency UPS features include higher power capacity compared to highfrequency units, greater surge capacity for sudden power demands, improved voltage regulation for stable and clean power supply, and enhanced reliability to withstand harshconditions. These systems are preferred in applications where reliability, capacity, and load compatibility are essential.
| Name | Certificate |
|---|---|
| Note | View Certificate |
| INPUT | |
|---|---|
| Operating voltage range (Vac) | 380/400 Vac (±20%), (3Ph+N + PE) |
| Power factor | ≥0.97 |
| Operating frequency range (Hz) | 50/60 (±0.05%) |
| OUTPUT | |
| Output voltage (Vac) | 220 Vac (±1%) |
| Crest factor | 3:1 |
| Harmonic distortion (THDv) | ≤2 (Linear load) |
| Output frequency (Hz) | 50/60 (±0.05%) |
| Efficiency (%) | 86 |
| PHYSICAL | |
| Shipping weight (kg) | 120 |
| Net weight (kg) | 110 |
| Dimension W*D*H (mm) | 305×585×864 |
| ENVIRONMENT | |
| Operating Temperature (ºC) | 0 ~ 40 |
| Noise level (dB) | <60 |
| Altitude (m) | <1500 |
| Humidity range (%) | 0 ~ 95 |
| Storage temperature (ºC) | -25 ~ 55 |
| SYSTEM FEATURES | |
| LED display | Low battery voltage, Mains status, Inverter, Bypass, UPS failure, Overload |
| LCD display | I/O voltage, Frequency, Battery voltage, Load percentage, Internal temperature |
| Communication interface | RS232, RS485, EPO, Dry contact, SNMP (optional) |
| Overload | 110%≤Load ≤150%/1min; >150%/200ms → Bypass |
| Transfer time (ms) | 0 |
| Technical | |
| Battery voltage (Vdc) | 192 |
| Capacity (kVA/kW) | 8/6.4 |
| STANDARDS | |
| EMC | IEC/EN 62040-2 (IEC 61000-4-2, 61000-4-3, 61000-4-4, 61000-4-5, 61000-4-6, 61000-4-8, 61000-4-11, 61000-2-2) |
| Performance | IEC/EN 62040-3 |
| Safety | IEC/EN 62040-1; IEC 62477-1 |