Industrial UPS | 10 kVA
Design: Online double conversion
Output: Pure sine wave
Cold Start: Battery/DC start
Input: Wide 304–456Vac, generator ready
Battery: ABM tech, long life
Charging: Fast float/boost
Isolation: Built-in transformer
Protection: Overload, short, temp, battery faults, auto bypass
Sync: Seamless bypass transfer
Management: LCD, RS232/485, SNMP (opt.), dry contacts
Netcon Offers low-frequency systems that ensure compatibility with various loads, providing higher reliability and efficiency Commonly used in critical applications like data centers, medical facilities, and industrial environments, low-frequency UPS features include higher power capacity compared to highfrequency units, greater surge capacity for sudden power demands, improved voltage regulation for stable and clean power supply, and enhanced reliability to withstand harshconditions. These systems are preferred in applications where reliability, capacity, and load compatibility are essential.
| Name | Certificate |
|---|---|
| Note | View Certificate |
| INPUT | |
|---|---|
| Operating frequency range (Hz) | 50/60 (±0.05%) |
| Power factor | ≥0.97 |
| Operating voltage range (Vac) | 380/400 Vac (±20%), (3Ph+N + PE) |
| OUTPUT | |
| Efficiency (%) | 86 |
| Output frequency (Hz) | 50/60 (±0.05%) |
| Harmonic distortion (THDv) | ≤2 (Linear load) |
| Crest factor | 3:1 |
| Output voltage (Vac) | 220 Vac (±5%)/ 230 Vac (±5%) |
| PHYSICAL | |
| Net weight (kg) | 115 |
| Dimension W*D*H (mm) | 305×585×864 |
| Shipping weight (kg) | 125 |
| ENVIRONMENT | |
| Humidity range (%) | 0 ~ 95 |
| Operating Temperature (ºC) | 0 ~ 40 |
| Storage temperature (ºC) | -25 ~ 55 |
| Altitude (m) | <1500 |
| Noise level (dB) | <60 |
| SYSTEM FEATURES | |
| Overload | 110%≤Load ≤150%/1min; >150%/200ms → Bypass |
| LCD display | I/O voltage, Frequency, Battery voltage, Load percentage, Internal temperature |
| Transfer time (ms) | 0 |
| Communication interface | RS232, RS485, EPO, Dry contact, SNMP (optional) |
| LED display | Low battery, Mains status, Inverter, Bypass, UPS failure, Overload |
| Technical | |
| Battery voltage (Vdc) | 192 |
| Capacity (kVA/kW) | 10/8 |
| STANDARDS | |
| EMC | IEC/EN 62040-2 (IEC 61000-4-2, 61000-4-3, 61000-4-4, 61000-4-5, 61000-4-6, 61000-4-8, 61000-4-11, 61000-2-2) |
| Safety | IEC/EN 62040-1; IEC 62477-1 |
| Performance | IEC/EN 62040-3 |