Netcon
Netcon Compact series NT33 -40KVA 3:3 Tower UPS
image
image
image
image

Netcon Compact series NT33 -40KVA 3:3 Tower UPS

10-40 KVA 3:3, 3:1 | 40KVA/36KW or 40KW

  • High Power Density: Compact design with high power output.
  • Parallel Redundancy: Supports N+X configuration with up to 4 units in parallel.
  • Double Conversion: Online double conversion with DSP control for high reliability.
  • Low Harmonic Distortion: Input current harmonic is less than 3%.
  • Wide Voltage Range: Operates from 208V to 478V AC input.
  • Battery Options: 0–30kVA: 16–20 pcs (up to 50); 40kVA: 30–50 pcs.
  • High Charging Current: Adjustable charging current up to 20A.
  • Generator Compatible: Designed to work with generator input.
  • Frequency Converter: Supports 50Hz/60Hz frequency conversion mode.
  • Load Handling: Capable of supporting 100% unbalanced load.
  • Guard: Protection against short-circuit, overload, overheat, battery issues, & fan faults.
  • Interfaces: USB, RS232/RS485, parallel port, dry contact, SNMP and relay card.
  • GBT Technology: Incorporates advanced GBT (Gate Bipolar Transistor) technology.
Applications: Data centers, telecom, healthcare, and industrial automation, Business and commercial use

Netcon 40 KVA 3:3 Phase Tower Mount Online UPS is a high-capacity, industrial-grade power backup system designed for large-scale critical applications. With a 3-phase input and 3-phase output configuration, it ensures balanced power distribution, high efficiency, and continuous protection for mission-critical systems in data centers, healthcare, telecom, and industrial operations.  UPS  is CE Certified and fully compliant with EMC & IEC safety and performance standards, ensuring global compatibility, safety, and reliability.

Powered by True Online Double Conversion Technology, it delivers uninterrupted, pure, and stable power with zero transfer time, ensuring complete protection against power fluctuations, surges, and blackouts. The External Battery Type design allows for the connection of scalable battery banks, offering customizable and extended backup times to meet specific operational needs.  Its advanced protection features, high efficiency (up to 95%), and scalable runtime make it a trusted power solution for industries where power continuity is critical.

This UPS offers customizable backup duration, flexible battery expansion, and smart remote monitoring, making it a versatile choice for large-scale, power-intensive applications in data centers, healthcare, telecom, industrial automation, and commercial buildings.

Name Certificate
LVD Test Report View Certificate
EMC Certificate View Certificate
LVD Certificate View Certificate
EMC Test Report View Certificate
MODEL
Capacity 40kVA/36kW or 40kW
INPUT
Frequency Protection Range 50/60Hz±10%
Bypass Voltage Range Max. voltage: 220V: +25% (Optional +10%, +15%, +20%) 230V: +20% (Optional +10%, +15%) 240V: +15% (Optional +10%) Min. voltage: -45% (Optional -20%, -30%)
Frequency Range 40-70Hz (50/60Hz Auto Sensing)
Power factor >=0.99
Voltage Range 305-478 VAC (Full load): 208-478 VAC (50% load):
Nominal Voltage (Vac) 380/400/415Vac (3Ph+N+PE)
ECO Range Same as bypass
Harmonic distortion (THDi) <=3% Linear load
OUTPUT
Frequency Range Line Mode: ±1%/±2%/±4%/±5%/±10% of the rated frequency (Optional) Battery Mode: (50/60 +0.1%) Hz
Power Factor 0.9
Voltage Range 380/400/415Vac (3Ph+N+PE)
Output waveform Pure Sinewave
Output Transfer Time AC mode to Bat.mode - 0ms Inverter to Bypass - 0 ms
Overload AC Mode : ≤110%,last 60min; ≤125%, last 10min; ≤150%, last 1 min; > 150% turn to bypass Immediately Battery Mode : ≤110%, last 10min; ≤125%, last 1min; ≤150%, last 5s; > 150% turn to bypass Immediately
Crest Factor 3:1
Harmonic distortion (THDv) <=2% Linear Load <=5% Non Linear Load
Voltage Regulation ±1%
Efficiency up to 94.5%
PHYSICAL
Approx. Net Weight 239/46KG
Approx. Dimension (D×W×H) Standard unit - 200 x 900 x 868 Long Run Unit - 250 x 580 x 655
BATTERY
Charging current (Max.) Standard Unit : 2.7A Long Run Unit 20A Max Can set according to battery capacity installed
Battery Voltage Standard Unit : +180Vdc (2x30pcs 12V9Ah) (2x30pcs 12V7Ah optional) Long Run Unit - 40KVA: +180/192/204/216/228/240/252/264/276/288/ 300Vdc(30/32/34/36/38/40/ 42/44/46/48/50pcs)
ENVIRONMENT
Altitude <1500m, derating required when>1500m
Operating temperature 0°C to 40°C
Noise level <64dB
Storage temperature -25°C~55°C
Humidity range 20~95%RH @ 0~40°C (Non condensing)
STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8