Netcon
Compact Series 3:3 - 60 KVA UPS
image
image
image
image

Compact Series 3:3 - 60 KVA UPS

50-200 KVA 3:3 | 60KVA

  • Control: Full digital control for stable and reliable performance
  • Wide input voltage range: 138-485Vac (phase voltage 80-280Vac); No derating > 305Vac.
  • Power saving: Inp. power factor up to 0.99; 3-level inverter, efficiency upto 95.5%.
  • Parallel redundancy function: Supports up to 6 units; allows parallel battery sharing.
  • Flexible battery configuration: Batteries number of each groupcan be selected from 30 pieces to 50 pieces. Large charging current can meet the requirement of long time back up. 
  • Strong load capacity: Output power factor=1.0. Supports unbalanced, inductive, and capacitive loads
  • Compatible with generator: Power walk-in reduces start current impact and generator size.
  • LBS function: Supports 2 synchronized UPS systems for improved reliability.
  • Communication: Support USB, RS485, RS232, SNMP, dry contact card. 
Applications: Business and commercial use

Netcon 60 KVA Online 3-Phase UPS is a high-capacity, fully automated power backup system designed to provide stable, uninterrupted, and clean power to critical systems. Built with advanced true double-conversion technology, it ensures zero transfer time, isolating connected equipment from power fluctuations, surges, and outages. This UPS is the ideal choice for data centers, healthcare facilities, industrial automation, telecommunications, and other mission-critical environments where operational continuity is paramount. With CE and IEC Certification,  Netcon  UPS guarantees global safety and performance standard.

Netcon 60KVA Online 3-Phase UPS is a powerful, scalable, and energy-efficient backup power solution. With its true double-conversion technology, robust design, and modular scalability, it guarantees uninterrupted power to mission-critical systems. Its energy-efficient design, redundancy features, and advanced battery management make it the preferred choice for industries like IT, healthcare, telecommunications, and manufacturing. Its ability to operate in harsh environments ensures 24/7 uptime, making it a vital component for large-scale infrastructure and critical applications.

Name Certificate
IEC certificate View Certificate
LVD certificate View Certificate
CE Certificate View Certificate
IEC Test Report View Certificate
INPUT
Nominal Voltage (Vac) 380/400/4 15Vac (3Ph+N+PE)
Power factor >= 0.99
Frequency Range 40~70Hz (50/60Hz Auto- Sensing)
Voltage Range 138~485Vacfor40% load; 305~485Vac for full-load
Harmonic distortion (THDi) <= 3% Linear load
Generator Input Input
Bypass Voltage Range Max.voltage:220V:+25% (Optional+10%,+15%,+20%) 230V:+20% (Optional+10%,+15%) 240V:+15% (Optional+10%) Min.voltage:-45% (Optional-20%,-30%)
Frequency Protection Range 50/60Hz±10%
OUTPUT
Frequency Range Line Mode: ± 1%/ ± 2%/ ± 4%/ ± 5%/ ± 10% of the rated frequency (Optional) Battery Mode - (50/60 ±0.2%)Hz
Overload AC Mode : Load «110%: last 60min, «125%: last 10min, «150%: last 1min, >150%:turn to bypass immediately By Pass Mode : 135% overload long time; >1000% overload 100ms
Crest Factor 3:1
Power Factor 1.0
Harmonic distortion (THDv) <= 2% with linear load <= 4% with non linear load
Voltage Regulation ±1%
Voltage Range 380/400/4 15Vac (3Ph+N+PE)
PHYSICAL
Approx. Net Weight 83KG
Approx. Dimension (D×W×H) 250 x 828 x 868
BATTERY
Battery Voltage Optional Voltage: ± 180/ ± 192/ ± 204/ ± 216/ ± 228/ ± 240/ ± 252/ ± 264/ ± 276/ ± 288/ ± 300Vdc(30/32/34/36/38/40/42/44/ 46/48/50pcs optional); 360Vdc~600Vdc (30~50pcs, 30pcs default, 36~50pcs output power factor 1.0; 32~34pcs output power factor 0.9; 30pcs output power factor 0.8)
Charging current (Max.) 20A Max. (charge current can be set according to battery capacity installed
ENVIRONMENT
Altitude <1500m, derating required when>1500m
Operating temperature 0°C~40C
Humidity range 0-95% (Non condensing)
Storage temperature 250 -550 (No battery)
Noise level <58dB
EFFICIENCY
Efficiency Up to 95.5%
STANDARDS
Safety IEC/EN62040-1, IEC/EN62477-1
EMC IEC/EN62040-2 (IEC 61000-2-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11)
SYSTEM FEATURES
Alarm Overload, utility abnormal, UPS fault, battery low, etc
Backfeed protection Support
Remote LCD Support
Communication USB, RS232, RS485, parallel port, dry contact, intelligent slot, LBS, SNMP card (Optional), relay card (Optiona)
Transfer time Utility to Battery: 0ms; Utility to Bypass: 0ms
Protection Short circuit, overload, over temperature, battery low, fan fault alarm