1-3KVA, 1:1 |1000VA / 900W
Netcon 1KVA Floor Mount Online UPS is a state-of-the-art power protection solution designed to provide continuous, clean, and reliable power for critical devices. Built with True Online Double Conversion Technology, it ensures zero transfer time, making it ideal for sensitive equipment that cannot afford even a momentary power disruption. With CE and IEC Certification, Netcon UPS guarantees global safety and performance standard.
Key features include a high output power factor (0.9/1.0), ensuring maximum usable power, and multi-layered protection against overload, short circuits, surges, and fluctuations. The LCD display provides real-time system status, while communication ports (SNMP, RS232, USB) enable remote monitoring and control.Designed for high efficiency (up to 95%), it reduces power consumption and operating costs. The automatic bypass function ensures continuous power in case of UPS failure, while generator compatibility allows smooth operation with generator power.
This UPS is available in both Inbuilt Battery and External Battery configurations. The Inbuilt Battery model is a compact, plug-and-play unit best suited for short backup needs in offices, homes, and POS systems. On the other hand, the External Battery model offers extended backup by allowing the connection of additional battery banks, making it perfect for data centers, telecom, industrial automation, and healthcare environments
| Name | Certificate |
|---|---|
| EMC Certificate | View Certificate |
| EMC Test Report | View Certificate |
| LVD Test Report | View Certificate |
| LVD Certificate | View Certificate |
| MODEL | |
|---|---|
| Capacity | 1000VA / 900W |
| INPUT | |
| Voltage Range | 110~300Vac (176~280Vac @ 100% load) |
| Power factor | >=0.9 |
| Nominal Voltage (Vac) | 208/220/230/240Vac |
| OUTPUT | |
| Output Transfer Time | 0 ms |
| Frequency Range | Line mode: 46~54Hz or 56~64Hz Bat. mode - (50/60±0.1%)Hz |
| Crest Factor | 3:1 |
| Power Factor | 0.9 |
| Harmonic distortion (THDv) | <=3% Linear Load <=5% Non Linear Load |
| Output waveform | Pure Sinewave |
| Voltage Regulation | ±1% |
| Transfer time | AC mode to Bat.mode - 0ms Inverter to Bypass - 4ms (Typical) |
| Voltage Range | 208/220/230/240Vac |
| PHYSICAL | |
| Approx. Dimension (D×W×H) | 144 x 293 x 209 |
| Approx. Net Weight | 9.3KG or 12.5KG |
| BATTERY | |
| Capacity (Standard unit) | 9Ah/12V (7Ah/12V optional) |
| Charging voltage | 27.4Vdc±1% or 41.1Vdc±1% |
| Charging current (Max.) | 1A |
| Typical recharging time | 4 hours (to 90% of full capacity) |
| Battery Number | 2-3 |
| ENVIRONMENT | |
| Noise level | <50dB at 1 Meter |
| Altitude | <1500m, derating required when>1500m |
| Operating temperature | 0°C to 40°C |
| Storage temperature | -25°C~55°C |
| Humidity range | 20~95%RH @ 0~40°C (Non condensing) |
| EFFICIENCY | |
| Battery mode | 85% |
| AC mode | 88% |
| INDICATORS | |
| LED Display (LED version) | Line mode, Bat.mode, ECO mode, Bypass mode, Battery low voltage, Overload & UPS fault |
| LCD Display (LCD version) | Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time |
| STANDARDS | |
| Safety | IEC/EN62040-1,IEC/EN62477-1 |
| EMC | IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8 |
| OTHERS | |
| KVA | 1-3 |
| Frequency Range | 46~54Hz or 56~64Hz |
| FREQUENCY | |
| Frequency range | 40~70Hz (50/60Hz Auto-Sensing) |